BrandschutzklappeBSKRPR
BrandschutzklappeBSKRPR
Your configured product
Brandschutzklappe BSKRPR
General product information
Einsatzgebiete
Fire dampers, installed in ventilation ducts (air conditioning systems), serve for the automatic locking of fire lobbies.
The BSK-RPR fire damper complies with the EN 15650 product standard.
The BSK-RPR has been tested according to EN 1366-2. CE marking and Declaration of Performance (DoP) according to the Construction Products Regulation. The classification according to EN 13501-3 is EI 30 (ve i↔o) S to EI 90 (ve, ho i↔o) S.
Wide range of uses and applications.
For optimum integration into the building management system using the SCHAKO EasyBus signalling and switching bus system or the SCHAKO BKSYS small fire damper control unit.
According to the Directive 2014/34/EU, EC conformity certificate number EPS 09 ATEX 2 153 X, the use in areas subject to explosion hazards is permitted as an ATEX variant.
Eigenschaften
- Round design.
- For automatic closure of fire sections.
- Connection of a smoke release device with abZ (e.g. SCHAKO smoke detection system RMS) in combination with suitable release devices (e.g. spring return actuator) also possible.
- Depending on the installation situation, classification according to EN 13501-3 is EI 30 (ve i ↔ o) S to EI 90 (ve , ho i ↔ o) S.
- Housing leakage class C according to EN 1751.
- Integration is possible into the building management system via the SCHAKO EasyBus signalling and switching bus system or the SCHAKO BKSYS fire damper mini-controller.
- Optional: Certified according to ATEX Directive 2014/34/EU.
Downloads
Tender texts